When power ignites

Yasser Amer Ahmed, Fire Protection Specialist, offers a technical and standards-based analysis of managing and minimising the risks of lithium-ion battery fires.

The proliferation of lithium-ion (Li-ion) technology is a cornerstone of the global transition to renewable energy and electrified transportation. From grid-scale Energy Storage Systems (ESS) and electric vehicles (EVs) to consumer electronics and micromobility devices, these high-energy-density batteries are ubiquitous. However, their inherent electrochemical composition presents a unique and potent fire hazard distinct from conventional combustibles. The self-sustaining phenomenon of thermal runaway triggered by internal short circuits, mechanical damage or thermal abuse can result in intense fires, the risk of hazardous projectiles and the violent release of toxic and flammable gases. Mitigating these risks requires a multi-faceted approach grounded in robust design standards, informed installation codes like NFPA 855 and evidence-based emergency response protocols.

The root cause: thermal runaway and its hazards

The principal failure mechanism in Li-ion batteries is thermal runaway. This exothermic, self-propagating reaction begins when a cell’s internal temperature rises to a critical point, often due to:

  • Thermal abuse: External fire exposure or operational overheating.
  • Electrical abuse: Overcharging, over-discharging or external short circuits.
  • Mechanical abuse: Penetration, crushing or deformation of the cell.

Once initiated, the heat generated decomposes the flammable organic electrolyte and various cell components. This process releases a complex mixture of toxic and combustible gases, including hydrogen (H₂), carbon monoxide (CO), methane (CH₄), and notably, hydrogen fluoride (HF). The pressure build-up within the cell casing leads to venting or rupture, ejecting burning material and exposing the highly flammable gases to ignition sources. As the Fire Protection Research Foundation’s (FPRF) full-scale testing demonstrated, even after initial knockdown, the deep-seated nature of a cell failure and the potential for re-ignition hours later due to residual heat pose a significant challenge for responders.

The hazards are multi-faceted:

  1. Intense fires and heat release: Tests on a 100 kWh commercial ESS (Tesla Powerpack) showed internal temperatures exceeding 2000°F (1093°C) during an externally ignited fire event.
  2. Toxic gas emission: The FPRF tests consistently detected hazardous levels of HF, a highly toxic and corrosive gas. During external fire tests, HF concentrations exceeded the detector’s maximum range of 100 ppm for over two hours. Internal failure tests also showed significant CO and CH₄ production.
  3. Projection of hazards: Cylindrical cell designs, such as the 18650 cells used in the tested ESS, have been shown in other research to potentially rupture violently, propelling projectiles considerable distances.

The first pillar of mitigation: design, testing and product certification

Effective risk mitigation begins long before installation, at the product design and certification stage. Key safety standards form a critical barrier:

  • UL 1973: Standard for Batteries for Use in Light Electric Rail (LER) and Stationary Applications. This is a foundational standard that includes stringent construction requirements and performance tests, most notably an external fire exposure test (simulating a hydrocarbon pool fire attacking the unit) and an internal fire exposure test (inducing a single cell into thermal runaway to ensure it does not cascade).
  • UL 9540: Standard for Energy Storage Systems and Equipment. This system-level standard evaluates the entire ESS assembly, including power conversion equipment (PCS), and references UL 1973 for the battery component. The new 2025 edition enhances clarity for buyers on system-level performance.
  • UL 9540A: This test method evaluates thermal runaway fire propagation in battery energy storage systems. It is not a pass/fail standard but provides critical data for Authorities Having Jurisdiction (AHJs) to assess the safety of a specific ESS installation, directly feeding into the requirements of NFPA 855.

Manufacturers incorporate safety features informed by these standards, such as:

  • Robust Battery Management Systems (BMS) to monitor voltage, current and temperature, preventing electrical abuse conditions.
  • Thermal Management Systems (e.g., liquid cooling, as featured in the tested Powerpack) to maintain optimal operating temperatures.
  • Venting and gas management pathways to safely direct and exhaust gases released during a failure away from occupants and other equipment.
  • Physical containment within steel enclosures and pods to prevent projectile hazards and contain initial failures.

The second pillar: regulated installation in accordance with NFPA 855

The National Fire Protection Association Standard 855, Standard for the Installation of Stationary Energy Storage Systems, is the paramount code for mitigating fire risks where these systems are deployed. It provides the necessary framework to address the unique hazards identified in research, translating laboratory findings into enforceable safety practices.

NFPA 855 mandates rigorous installation requirements based on the ESS’s chemistry, size and location:

  1. Separation and clearance: The standard specifies minimum separation distances between ESS units, from building features and from property lines. This is directly informed by test data, such as the observed flames emanating from the front door and exhaust vent of the Powerpack. NFPA 855 ensures the recommended clearances (e.g., 3 ft from building openings) are codified and adhered to, limiting flame spread and radiant heat exposure.
  2. Fire suppression and detection: NFPA 855 requires listed smoke detection systems within ESS rooms or units. For larger installations, automatic fire suppression systems, typically water-based, are mandated. The standard acknowledges that while large-flow water is often recommended, other agents like water mist or encapsulating agents may be deployed to aid cooling and prevent re-ignition. The FPRF test conclusion that “water can be an effective extinguishing agent on large format Li-ion battery fires, however, large quantities may be required for extinguishment” underscores the necessity of designed suppression systems.
  3. Hazard Mitigation Analysis (HMA): For larger systems, an HMA is required to identify specific hazards and propose engineered safety designs, which may exceed the prescriptive requirements of the standard. This performance-based approach is crucial for innovative or very large-scale installations.
  4. Venting and emergency planning: The standard addresses the need for ventilation to manage the release of toxic gases (like HF) and requires signage indicating the presence of Li-ion batteries and their associated hazards for first responders.

The third pillar: emergency response and recovery

Even with perfect prevention and protection, the risk of an incident remains. Therefore, informed emergency response is a critical component of mitigation.

  • Recognition: Responders must be trained to identify Li-ion ESS installations and understand the associated risks: thermal runaway, toxic gas production and electrical hazards.
  • Suppression tactics: Large-flow water remains the primary recommended medium for cooling and suppressing Li-ion fires, as it addresses the root cause of thermal runaway: heat. However, as noted in the FPRF report, immense quantities may be required. The practice of submerging damaged EVs or ESS units is increasingly discouraged due to issues of contaminated run-off, impracticality and unresolved re-ignition risk. Targeted solutions, such as fire-resistant containers that apply directed water mist and capture runoff, are emerging as best practices.
  • Personal Protective Equipment (PPE): The documented release of HF at levels far exceeding OSHA exposure limits mandates that responders must use Self-Contained Breathing Apparatus (SCBA) throughout the incident and during overhaul.
  • Overhaul and recovery: The re-ignition potential necessitates prolonged monitoring with thermal imaging cameras. Secure, fire-resistant storage for damaged units must be planned for post-incident.

Mitigating the risk of Li-ion battery fires is not a single-action task but a continuous process of defense-in-depth. It originates with robust, third-party-certified product design tested to standards like UL 1973 and UL 9540A. It is enforced through meticulous installation practices codified in NFPA 855, which mandates separation, detection, suppression and ventilation based on empirical fire test data. Finally, it is sustained by equipping emergency responders with the knowledge, tactics and equipment to manage incidents effectively and safely. As the technology and deployment scales continue to evolve, so too must the synergistic relationship between research, standards development and field practice to ensure safety keeps pace with innovation.

This feature appeared in issue 68 of Fire Middle East magazine.