Fire curtains are increasingly specified across the region’s open, high-rise, and mixed-use buildings. Ahmed Yousry examines how they are tested, how their performance is classified and certified, and why differences between applicable standards matter at specification and approval.
Image courtesy of Coopers Fire

Fire curtains have become a familiar feature of contemporary building design across the Middle East, allowing architects to keep spaces open – atria, lobbies and circulation routes – while preserving the compartmentation and escape provisions that fire strategies depend on. It is easy to think of a fire curtain as a single component: a sheet of fire-resistant fabric that drops from a ceiling when an alarm sounds. In reality, it is an assembly of parts that must work together, and its performance is inseparable from how it is installed, integrated and maintained. That distinction frames the question at the heart of every specification: when a curtain is called up with a stated fire performance, what evidence actually demonstrates it? The answer turns on which standard the product was tested and certified against — and the standards in common use are not the same.

What a fire curtain does

Fire curtains are a form of passive fire protection: their role is to contain a fire rather than to detect or fight it. Concealed within a ceiling or wall during normal use, the curtain deploys when triggered by a fire alarm, forming a barrier of fire-resistant fabric that resists the passage of flame, heat and in some special designs, smoke. Because they perform the same containment function as fire-rated walls, doors or glazing, curtains can substitute for those permanent elements, which is why they are used to protect means of escape, to maintain compartment lines, to close off atria and vertical voids, and to separate corridors, stairwells and lift lobbies. They are produced in vertical, horizontal and concertina configurations to suit the geometry of the opening. What matters for safety is not the fabric alone but the complete system: the components, the substrate they are fixed to, the way the curtain is integrated into the building, and its ongoing servicing.

What a fire test actually shows

The most useful way to read any test is to ask what it demonstrates. Furnace exposure, the fire-resistance test most people picture, establishes how a specimen resists fire for a period, but it is only one measure of a curtain’s behaviour. Depending on the standard applied, a test regime may also examine how the system operates in service and how it deploys in an emergency: whether the fabric stays within its side guides under impact; how fast the curtain descends and how quickly it begins to deploy; whether it will still deploy if power is lost; whether the motor continues to function at elevated temperature; how the fabric itself behaves in terms of reaction to fire; how much smoke passes the barrier; and how ancillary items such as controls and retract buttons perform. A furnace test result and an operational test regime answer different questions, and a curtain’s real-world reliability depends on both.

Image courtesy of Coopers Fire

Why the standards differ

Several standards are referenced for fire curtains in the region: BS 8524, EN 16034, EN 1634, ISO 21524 and the UL 10D. Each evaluates fire resistance in some way, but their scope varies considerably. Some assess performance essentially during a fire; others extend to the product’s operational life, from routine cycling through to emergency deployment. Understanding which aspects a given standard addresses and which does not is central to interpreting any test evidence offered in support of a curtain. The differences are easiest to see side by side.

Test aspectBS 8524ISO 21524EN 16034*UL 10DEN 1634-1
Durability sampling, full scale, pre-furnace1,000 cycles (10m x 10m)1,000 cycles (10m x 10m)000
Cycling before fire test25 cycles25 cycles25 cycles3 cycles25 cycles
Deployment start time< 3 seconds< 10 secondsNot timed——
Descent speed controlledWithin 2 m of floorYes—Stated (inch/s)—
Gravity fail-safeYesYes———
Elevated-temperature motor (to 400 °C)YesYes———
Impact testYesYes———
Fabric reaction to fireEN 13501-1ISO 1182 / 1716———
Smoke-leakage methodEN 1634-3YesYesUL 1784—
Installation & servicing standardBS 8524-2YesFactory production control——
Products specifically includedVertical, Horizontal, Concertina Type & Egress doorVertical, Horizontal, Concertina Type & Egress doorVerticalVerticalVertical

Selected technical differences between the standards commonly applied to fire curtains. A dash indicates the aspect is not specified in the source material and does not imply that a standard prohibits or omits the feature.

*EN16034 is a product standard that refers to EN1634-1 & EN1634-3

Reading the differences

Some of these divergences have direct practical consequences. Deployment timing is one: where one standard requires the curtain to begin deploying within three seconds of triggering, another allows up to ten. In everyday terms, the gap sounds small, but in the first seconds of a fire, when smoke moves fast, several seconds can determine whether smoke is held within the intended compartment. The specimen tested is another point of divergence. Under some regimes, the curtain is cycled extensively before it is fire tested: the largest certified size, up to 10 m × 10 m, is cycled a thousand times and then cut down for the furnace test, so that an aged sample is exposed to fire; the testing laboratory will select the section of fabric that demonstrates the most wear and tear and is therefore most likely to fail; others test a new or lightly cycled specimen. These represent different testing philosophies rather than differences of degree. Features such as gravity fail-safe operation, an elevated-temperature motor test and an impact test appear in some standards and not in others, and the smoke-leakage methods are not directly comparable: one measures leakage around linear edges, another across the whole surface area of the curtain.

Equivalence therefore cannot be assumed. A concern that BS 8524 and EN 16034 might conflict was examined, which concluded there is no conflict. EN 16034 applies specifically to doors and shutters intended for the movement of people, whereas BS 8524 applies to active fire-curtain barrier assemblies. The two address different applications rather than offering interchangeable evidence. The field of application has limits, too: there is no recognised method to extrapolate insulation (EI) ratings beyond the tested curtain size, and for curtains larger than the size tested. Extended-application testing can support some larger installations, but only within defined bounds.

Image courtesy of Coopers Fire

From testing to certification

A successful test is not the same as a certified system, and the two should not be presented as equivalent. A test report and a classification describe how a particular specimen behaved under defined conditions; certification, together with the controls around manufacture and installation, addresses whether the product placed in a building will reproduce that behaviour. Installation is decisive here; a curtain installed differently from its tested configuration may not perform as the test suggests. Some standards extend beyond the fire test to cover installation, commissioning, inspection and servicing, or reference factory production control; others do not. Where a product is certified, the certification scheme and the third-party body behind it form part of the evidence a reviewer should understand, alongside the test report and the classification.

Classification and application

The practical starting point is the performance required at each opening. Under the European classification system, fire-resistance performance is expressed as integrity (E, resisting the passage of flame and hot gases), radiation (EW, integrity together with a limit on transmitted radiant heat), insulation (EI, limiting the temperature rise on the unexposed face) and smoke control (Sa, limiting the passage of smoke). These are not interchangeable, and the appropriate classification depends on the curtain’s role in the fire strategy. Insulation offers the highest level of thermal protection, but insulated curtain systems remain comparatively specialised and heavier, with larger headboxes — so for many escape applications a radiation classification is used in conjunction with tenability criteria that keep conditions on the non-fire side survivable. The essential point for anyone specifying or approving a curtain is that these terms’ reaction to fire and fire resistance, integrity and insulation, testing and certification — carry precise meanings and should not be used loosely.

The rating is not the whole story

A declared fire rating, on its own, does not tell the complete story. The test standard, the tested configuration, the classification and its duration, the scope of application, and the certification evidence all need to be read together. Because the standards differ in what they assess – some only during a fire, others across a product’s operational life – a result under one standard cannot be assumed to demonstrate compliance with another. For the consultants, contractors, certification professionals and authorities specifying and approving fire curtains across the region, reading the whole evidence chain, rather than the headline rating, is what turns stated performance into a demonstrated one.